Code Considerations
Entrances
The number of barrier-free entrances into a building shall conform to table 3.8.1.2
One of the barrier-free entrances shall be the principal entrance to the building

Washrooms
The number of universal washrooms in a building shall conform to table 3.8.2.3.A
A barrier-free path of travel shall be provided to barrier-free washrooms designed to accommodate persons with disabilities

Doorways
Clear width of not less than 860mm when door is in open position as per 3.8.3.3.(1)

Activation Switches

Round Switches
Switch shall be a minimum of 150mm in diameter as per 3.8.3.3.(17)(a)(i)
Shall be a minimum of 600mm away from door jamb
Shall be a maximum of 1500mm away from door jamb
Shall be a minimum center height of 900mm from floor
Shall be a maximum center height of 1050mm from floor

Rectangular Switches
Rectangular switch shall be a minimum of 50mm in width & 100mm in height as per 3.8.3.3.(17)(a)(ii)
Shall be a minimum of 600mm away from door jamb
Shall be a maximum of 1500mm away from door jamb
Shall be a minimum center height of 900mm from floor
Shall be a maximum center height of 1050mm from floor

Elongated Switches
Switch shall be a minimum of 150mm in width
Switch shall be a minimum of 725mm in height
Shall be a minimum of 600mm away from door jamb
Shall be a maximum of 1500mm away from door jamb
Top shall be a minimum height of 900mm from floor
Top shall be a maximum height of 1050mm from floor
Bottom shall be a maximum height of 200mm from floor

Timing
As per BESAM SW100 Installation Manual
Opening Time
Door swings open within three to six seconds
(as adjusted)
Applies for closing time as well

Open Time
Door held open for 1.5 to 30 seconds (as adjusted)
Exit Devices
A door is required to be equipped with panic hardware or fire exit hardware (100 occupants or more) on assembly, educational, and daycare occupancies
The device must meet the following criteria:
- Actuating portion of a push-pad or cross bar will cover not less than half the width of the door
- Will be mounted not below 865 mm (34 in.) and not more than 1220 mm (48 in.) above the finished floor
- Be constructed to release with not more than 66 N (15 lbf) in the direction of egress
7.2.1.7−Panic Hardware (exit) and Fire Exit Hardware (cUL exit)